The images are published in their most up-to-date form. If an image appears outdated, open it in a new tab and refresh the image page to access the latest version. Alternatively, the quickest method is to open the site in an incognito window, as your browser may have cached the old image and might not replace it with the new one.

Why Use This Temperature Wet Bulb Calculator?

Wet Bulb Calculator

Wet Bulb Temperature
--

Formulas and Methodology

1. Wet Bulb Calculation (Stull, 2011):

The full equation used for the calculation is displayed below. Note that atan represents the arctangent function, T is Air Temperature (°C), and RH is Relative Humidity (%):

Tw = T * atan[0.151977 * (RH + 8.313659)^0.5] + atan(T + RH) - atan(RH - 1.676331) + 0.00391838 * (RH)^1.5 * atan(0.023101 * RH) - 4.686035
2. Dew Point to Humidity Conversion:

Used when Dew Point is provided instead of Humidity (Alduchov & Eskridge, 1996):

RH = 100 * (EXP((17.625 * Td)/(243.04 + Td)) / EXP((17.625 * T)/(243.04 + T)))